READ AND SAVE THESE INSTRUCTIONSHUMIDI-TECH andHUMIDI-TECH DIELECTRIC STEAM HUMIDIFIERSHT modelsInstallation, OperationandMaintenance Manual®HT(HT)_IO
10Notes:• Use DRI-STEEM's hard pipe adapter kit toconnect the steam outlet to hard pipe. Use a hoseclamp to connect the steam outlet to vapor hos
11HUMIDI-TECH® DISPERSIONNotes:• Use DRI-STEEM's hard pipe adapter kit to connect the steam outlet to hard pipe. Use a hose clamp toconnect the s
12HUMIDI-TECH® DISPERSIONRAPID-SORB dispersion assemblyCondensate drain DN20 (3/4" thread)Notes:• Use DRI-STEEM's hard pipe adapter kit to c
13HUMIDI-TECH® DISPERSIONDrip tee installationInstall a drip tee as shown below when the humidi-fier is mounted higher than the dispersion device,when
14IntroductionAfter the system has been properly installed andconnected to both electrical and water supplies, itmay be started.Start-up and checkout
15VAPOR-LOGIC®3 controlVAPOR-LOGIC3 is the standard controller for theHUMIDI-TECH. For more information regarding theoperation of the VAPOR-LOGIC3 mic
16HUMIDI-TECH® MAINTENANCEThe best way to determine how often your particularsystem will need maintenance is to remove thecover and inspect it after i
17HUMIDI-TECH® MAINTENANCEStandard water models(HUMIDI-TECH®, continued)2. Loosen the four cover bolts and remove thecover assembly from the tank.3. C
18HUMIDI-TECH® MAINTENANCEDI water models (HUMIDI-TECH® DI)The HUMIDI-TECH DI unit uses DI/RO water.Because these water types are mineral-free,cleanin
19HUMIDI-TECH® TROUBLESHOOTING GUIDENote: Probe rod corrosion or aging probe head material may cause level control system failure. Thisgenerally does
2TABLE OF CONTENTSTo the purchaser and installerThank you for purchasing our HUMIDI-TECH® humidifier. We have designed and built this equipment togive
20MELBORPESUACELBISSOPNOITCADEDNEMMOCERtonlliwreifidimuH.taehremrofsnartlortnoC .rekaerbtiucricremrofsnartlortnocteseRgnillactonsitatsidimuH .tatsidim
21HUMIDI-TECH® REPLACEMENT PARTSOM-778-1HUMIDI-TECH DI modelHUMIDI-TECH® standardwater modelNote: Refer to the tables on the next page for replacement
22HUMIDI-TECH® REPLACEMENT PARTSHUMIDI-TECH® replacement parts (refer to the drawing on previous page)* Specify humidifier model and serial numberswhe
23HUMIDI-TECH® REPLACEMENT PARTSHUMIDI-TECH® subpanel with SSRHT-OM-001* Refer to model for correct selection and quantity..oNnoitpircseD.ytQ.oN.traP1
2440/40AveR602-000098.oNtraPynapmoCreifidimuHMEETS-IRD4002©TWO-YEAR LIMITED WARRANTYDRI-STEEM Humidifier Company (“DRI-STEEM”) warrants to the origina
3HUMIDI-TECH® HUMIDIFIER OVERVIEWDeionized water models(HUMIDI-TECH DI)The HUMIDI-TECH DI, shown here,is specifically designed for use withdeionized o
4HUMIDI-TECH® DIMENSIONS50 mm409 mm57 mm472 mm146 mm38 mmVentingDN20 (¾") tank drainDN20 (¾") frame drain57 mmDC-116713 mm hole in basefor w
5HUMIDI-TECH® SPECIFICATIONSElectrical specifications, capacities and weightsTable notes:All HUMIDI-TECHs operate at 50/60 Hz.* For wire sizing, the h
6HUMIDI-TECH pipingWater makeup piping may be of any code-approved material (copper, steel, or plastic). Thefinal connection size is DN10 (3/8").
7HUMIDI-TECH® PIPINGNotes:• Offset humidifier from spill funnel or floor drain to prevent flash steam from rising into the cabinet.• Dashed lines indi
8HUMIDI-TECH® PIPINGHUMIDI-TECH DI (deionized/reverse osmosis water) field piping overviewDN10 (3/8") connection to watersupply line; water press
9HUMIDI-TECH wiringAll wiring must be in accordance with allgoverning codes, and with the HUMIDI-TECH® orHUMIDI-TECH DI wiring diagrams. The diagramsa