
Page 24 • DRI-STEEM Vaporstream humidifier
Calculating non-wetting distances
Sample exercise
Read through this exercise to learn more about specifying a
dispersion unit based on non-wetting distance. Assume you have
chosen to use Ultra-sorb units because you want pre-assembled
panels.
Assume the entering air is 20% RH, and the leaving air needs to
be 70% RH. Design for a non-wetting distance of 24" (610 mm)
maximum.
Solution
Refer to Figure 25-1. Find 20% entering RH. Proceed vertically until
you intersect the 70% leaving RH line. Draw a line horizontally
from that point to the right to see that for 24" (610 mm) of non-
wetting distance, 6" (152 mm) tube spacing would be the closest
match.
Verify capacity
From Table 25-1, note that for 6" (152 mm) spacing, maximum
capacity is 18 lbs/hr/ft
2
(88 kg/h/m
2
). Multiply this value by the
active face area of the Ultra-sorb to determine if the unit will
produce adequate output capacity. If the capacity is inadequate, go
to the next smaller tube spacing.
Steam absorption considerations
1. Non-wetting distance is the dimension downstream from the
leaving side of the steam dispersion assembly to the point where
wetting will not occur, although wisps of steam may be present.
Solid objects at duct air temperature, such as coils, dampers,
fans, etc., downstream of this dimension will remain dry.
2.
CAUTION! Non-wetting distances described in this catalog
do not apply when installing a steam dispersion assembly
upstream of filter media. If you need to install a steam dispersion
assembly upstream of filter media, consult your representative or
DRI-STEEM directly for special recommendations.
3. Note that the rise (Δ) in RH (the difference between entering
and leaving RH) has a direct bearing on the non-wetting
distance. As the rise increases, more vapor needs to be dispersed
into the air, and thus the non-wetting distance increases.
4. Uneven airflow over the cross-section of a dispersion assembly
can result in nonuniform mixing of steam with air which, in
turn, will adversely affect the non-wetting distance.
mc_042710_0850
Notes:
• Final equipment selection should account for
condensate loss. See the
DRI-STEEM Design
Guide
for steam loss tables.
• Dispersion assembly should accommodate
maximum output capacity of humidifier.
Guaranteed absorption
• Cataloged and guaranteed steam absorption
distances
• Unique tubelets in dispersion tubes eliminate
condensate drips
• Published absorption tables for sizing and
selecting the correct dispersion option
• Dri-calc
®
software available for system
selection and absorption distance calculations
Commentaires sur ces manuels