Page 26 • DRI-STEEM Vaporstream humidifier
Ultra-sorb dimensions
mc_050808_1215
Ultra-sorb LV
• Vertical dispersion tubes
• Suitable for AHUs or ductwork
• Use when duct height is greater than duct
width
• May use with pressurized or evaporative
steam (horizontal airflow only)
For Ultra-sorb Model LH (horizontal tubes), see the
Ultra-sorb Steam Dispersion Panels Product Catalog
(available at www.dristeem.com).
Figure 26-1:
Ultra-sorb LV dimensions
Top view
Header enclosure
Mounting flange
Condensate header
Elevation view
Dispersion tubes
Side view
A
D
B
G
A'
E
G
C
F
B'
H
E
Table 26-1:
Evaporative steam header capacities
Header capacity Header diameter
lbs/hr kg/h inches DN
300 135 3 80
600 270 4 100
1100 500 5 125
1850 820 6 150
Supply header
OM-123
Table 26-2:
Ultra-sorb LV dimensions
Dimension Inches (mm)
A
Overall width
15" (380) min, 147" (3735) max, in 1" (25) increments
A' Face width
12" (305) min, 144" (3660) max, in 1" (25) increments
B
Overall height
21" (530) min, 156" (3960) max, in 1" (25) increments
Panels with overall height more than 98" (2490 mm) are shipped unassembled.
B' Face height
12" (305) min, 144" (3660) max, in 1" (25) increments
C Steam inlet diameter
Determined by maximum steam capacity
D Condensate drain
¾" pipe thread (DN20)
E
Header enclosure
(front to back)
For 3" (DN80) and 4" (DN100) headers, E = 5" (127); for 5" (DN125) header, E = 6" (152); for 6" (DN150) header, E = 7" (178)
F
Header enclosure
(top to bottom)
For 3" (DN80) header F = 4.5" (114); for 4" (DN100) header, F = 5.5" (140); for 5" (DN125) header, F = 6.5" (165); for 6" (DN150) header F = 7.5" (191)
G
Flange
1.5" (38)
H
Condensate header
enclosure
4.5" (114)
Note: Header dimensions are determined by capacity. See Table 26-1.