Vue de la page 4
5
VAPOR-LOGIC
®
2
CONTROL BOARD INSTALLATION
The VAPOR-LOGIC
2
control board is shipped factory
mounted within a control cabinet with all internal wiring
completed. All software has been custom programmed
into your VAPOR-LOGIC
2
system according to the original
order requirements. Refer to the VAPOR-LOGIC
2
control
board drawing for detail of the board and connection
points. (See figure 5-1.)
Never run control system wires bundled with, or in
the same conduit as, line voltage wires.
All humidifier power wiring is represented on the
humidifier wiring diagram. A wiring diagram and
installation guide is attached to the inside of control
cabinet door. All instructions should remain in the
control cabinet after installation.
VAPOR-LOGIC
2
CONTROL BOARD OPERATION
No. Description
No. Description
Figure 5-1: VAPOR-LOGIC
2
printed circuit board
OM-613
J1 Alphanumeric Display Module Connector
J2 Removable Terminal Strip to Reline Control Signals
J3 Jumper PIN Selects Temperature Compensation Signal
J4 Jumper PIN Selects High Limit Humidity Signal
J5 Jumper PIN Selects Control Input Signal
QC-1 Heat 24 Volt Output to Heater Contactor
QC-2 Drain Drain Value 24 Vac Output
QC-3 Fill Fill Valve 24 Vac Output
QC-4 +21V 21 Volt DC Output to Freeze Stat
QC-5 FRZ Receives 2, 21 VDC Input From Freeze Stat
QC-6 BR Water Level, A
QC-7 OR Water Level, B
QC-8 V10 Water Level, C
QC-9 YEL Water Level Common
QC-10 +SSR Modulating 1-9 VDC, DC Output
QC-11 24H 24 Vac Hot
QC-12 24H 24 Vac Hot
QC-13 COM 24 Vac Common