P a g e 1 4 • D R I - S T E E M V a p o r s t r e a m h u m i d i f i e r
Va p o r s t r e a m c o n t r o l c a b i n e t s
Control cabinet features
The standard Vaporstream control cabinet is an ETL- and
C-ETL-listed NEMA-12 cabinet and is shipped loose. Control
cabinet options include:
• Factory mounting on humidifier
• NEMA-4 cabinet
• Cabinet door interlock switch
• Cabinet door lock
The control cabinet's size is based on capacity and system options.
See Table 14-1 below and Table 12-1 on Page 12 for cabinet sizing
by model.
The control cabinet can be mounted up to 50' (15 m) from the
Vaporstream. The keypad can be mounted up to 500' (152 m) from
the control cabinet. (Distances are based on wire/cable lengths.)
Figure 14-2:
Typical control cabinet layout
Table 14-1:
Standard control cabinet dimensions and weights
Cabinet
size
Cabinet dimensions Shipping weight*
inches mm lbs kg
S 16 h x 14 w x 6 d 406 h x 356 w x 152 d 32 15
M 20 h x 20 w x 7 d 508 h x 508 w x 178 d 55 25
L 24 h x 24 d x 7 d 610 h x 610 w x 178 d 73 33
XL 30 h x 24 w x 9 d 762 h x 610 w x 229 d 91 41
XXL 36 h x 30 w x 9 d 914 h x 762 w x 229 d 136 62
Notes:
* In addition to shipping weight of humidifier
Figure 14-1:
Vaporstream model 6-1 with mounted
control cabinet
Low voltage
(control wiring)
High voltage
(power wiring)
Shield
ground
lug
Control block
Relay
Transformer
Power block
Power ground
lug
Fuse blocks
Contactors
Machine ground lug
Vapor-logic
3
control board