D R I - S T E E M V a p o r s t r e a m h u m i d i f i e r P a g e 2 3
Figure 23-1:
Field piping overview Vaporstream Model VLDI (DI/RO water models)
Figure 23-1 notes:
Locate air gap only in spaces with adequate temperature and air movement to absorb flash steam; otherwise, condensation may form on nearby surfaces.
Refer to governing codes for drain pipe size and maximum discharge water temperature.
Offset humidifier from floor drain to prevent flash steam from rising into the humidifier.
Dashed lines indicate provided by installer.
The water supply inlet is more than 1" (25 mm) above the overflow port, eliminating the possibility of backflow or siphoning from the tank. No additional
backflow prevention is required; however, governing codes prevail.
Damage caused by chloride corrosion is not covered by your DRI-STEEM warranty.
See the previous page for recommended water supply piping for Model VLC (standard water system).
VLC-OM-011
Va p o r s t r e a m M o d e l V L D I p i p i n g
Notes:
Locate air gap only in spaces with adequate temperature and air movement to absorb
flash steam; otherwise, condensation may form on nearby surfaces. Refer to governing
codes for drain pipe size and maximum discharge water temperature.
Use this piping configuration when water seal must be elevated above flow line of
drain connection, such as when the humidifier is mounted near the floor.
Dashed lines indicate provided by installer
Figure 23-2:
Alternate water seal and drain valve piping
Skim/overflow outlet
Open drain required. See first note below.
Air gap
Drain
connection
H1 (see table on Page 22)
Top of water seal must be
below skim/overflow outlet
VLC-OM-012
Figure 23-3:
VLDI Models 2-1 through 5-1 piping
OM-4004
Drain valve
Fill
valve
Skimmer port
Drain piping
Install level
Install level
¾" (DN20) minimum
condensate drain piping rated
for 212 °F (100 °C)
Air vent height must
be equal to or greater
than dimension H2
(see table pn Page 22).
Air
vent
tube
Optional condensate
return piping from
dispersion
unit
Steam outlet
¾" (DN20) min. drain overflow
piping rated for 212 °F (100 °C)
¾" (DN20)
drain valve
If run is over 10' (3 m), increase
pipe to 1¼" (DN32)
Flow line of drain piping after the water
seal must be below the drain valve to
ensure that humidifier drains correctly
1" (25 mm) air gap
¾" pipe thread
(DN20) dispersion unit
condensate return inlet
Overflow
Strainer, by installer
6"
(150 mm)
minimum
Water supply line; water pressure range 25 psi to 80 psi (172 kPa
to 552 kPa); first 3' (1 m) is recommended to be stainless steel
tubing with a 2" (50 mm) water seal or loop in the supply line to
isolate steam during DI/RO water system maintenance
Drain piping
flow line
Pitch 1/8
"
/ft (1%)
Open drain required. See first note below.
H1
(see
table
below)