Table 81-1:
Multi-tank fieldbus profiles
Item Description Modbus
register
BACnet BACnet description LonTalk
MT_ACTIVE_FAULT_EXISTS_SOMEWHERE TRUE when there is an active fault
on 1 or more units in the MT group
DI:10
10010
BI-08 MT_active_fault_in_
system
nvoMT_
AlarmSomewhere
MT_ACTIVE_MESSAGE_EXISTS_SOMEWHERE TRUE when there is an active
message on 1 or more units in the
MT group
DI:11
10011
BI-09 MT_active_message_
in_system
nvoMT_MsgSomewhere
MT_SYS_OUTPUT_MASS_HR Actual steam production of the
system (mass/hr)
IR:23
30023
AI-08 MT_steam_demand_
mass
nvoMT_SteamOutMass
MT_SYS_OUTPUT_LBS_HR Actual steam production of the
system (lbs/hr)
IR:24
30024
MT_SYS_OUTPUT_PCNT Actual steam production of the
system (% of system capacity)
IR:25
30025
AI-09 MT_steam_demand_
percent
n v o M T _ S t e a m O u t p u t %
MT_RUNMODE MT runmode 1=run, 0=standby HR:14
40014
MSV-02 MT_Runmode values:
1)System Standby 2)
System Auto
nviMTRunMode
nvoMTRunMode
MT_STEAM_REQ_MASS_HR The fieldbus request for steam
(lbs/hr)
HR:15
40015
AV-14 MT_steam_output_
req_mass
nviMT_FbusDemndMass
MT_STEAM_REQ_LBS_HR Fixed units. The fieldbus request
for steam (lbs/hr)
HR:16
40016
MT_STEAM_REQ_SYS_PCNT The fieldbus request for steam (%
of system)
HR:17
40017
AV-15 MT_steam_output_
req_pcnt
nviMT_FldBusDemand%
Other system parameters and
interoperability
General system parameters are set the same as
for stand-alone tank/controller. See the Setup
section of this manual for instructions.
Multi-tank operation with Web interface
If you plan to use the Web interface for multi-
tank operation, the web interface must first be
configured, see
Web interface communication
on
Page 21.
To change a priority group, go to the Setup menu to access
Multi-tank setup/Tank priority group.
To add a tank to a multi-tank system:
1. Verify that the new tank has the correct tank designator.
Change, if necessary, before wiring in Step 2.
2. Connect wiring of new tank.
3. The master controller automatically adds the new tank’s
capacity into the total system capacity.
To permanently remove a tank from a multi-tank system:
1. Disconnect control board wiring (location P8) of the tank being
removed.
2. Reset system capacity from the Multi-tank setup menu. The
controller will automatically calculate the new system capacity.
Important:
t &BDIUBOLJOBNVMUJUBOLTZTUFNNVTUIBWFBVOJRVFUBOL
designator (A, B, C ... P). Duplicate tank designations will cause
multi-tank mode to operate incorrectly.
t &BDI7BQPSMPHJDCPBSETIJQTXJUIBOFUXPSL*1BEESFTTPG
192.168.1.195. When installing on an Ethernet network, assign
each board a unique IP address to avoid conflict with other
devices on the network.
Operation