Installation and Operation Manual
SSR modulation
DRI-STEEM electric humidifiers are available with two basic
types of solid state relay (SSR) modulation: SSR modulation with
contactors and 100% SSR modulation.
SSR modulation with contactor sequence
On systems that employ SSR modulation with contactors, the
operation of the unit is the same as with TP modulation. In this
scenario, one of the cycling contactors is replaced with an SSR. The
SSR now is the device that carries out all of the cycling duties. The
contactors are always either on or off. Any needed TP cycling is
handled by the SSR stage.
This provides two distinct advantages over standard TP modulation.
First, an SSR can turn on and off much faster than a contactor can.
Therefore, as the unit modulates around a demand signal, tighter
control is achieved because the cycle time on an SSR system can be
as low as one second (factory set at two seconds). This means that
every two seconds, the controller can adjust the on and off times of
the SSR to closely track desired demand.
The second major advantage over standard TP modulation is
reliability. With a solid state device like an SSR, component wear
is almost nonexistent compared with an electromechanical device
such as a contactor. Therefore, with the SSR doing all of the heavy
cycling work, the life expectancy of the contactors is extended.
100% SSR modulation
The ultimate in electric humidifier modulation is 100% SSR
modulation. With this type of control, all heat stages are controlled
by SSRs. This allows the output of the humidifier to track the actual
demand closely because all heat stages now can cycle on and off at
the rapid SSR cycle rate.
With 100% SSR modulation, a contactor is wired in series with
the SSR devices as an additional safety feature. If an SSR fails, the
controller will de-energize the contactor, which will de-energize the
heaters.
VL3_IOM.pdf 10 11/19/2009 9:11:05 AM