3. If using the service pin to identify the board on the network,
press the service pin (next to the blinking LED on the main
board).
4. Repeat steps 1–3 for the display. The service pin for the display is
an unmarked key on the keypad (see Figure 37-1).
Add a functional block
1. Drag and drop a “Functional Block” to the LonMaker drawing
window (see figure on Page 36).
2. The New Functional Block Wizard appears. Select the name
given to the main board device; then select the “Create shapes
for all network variables” check box.
3. Repeat steps 1–2 for the display.
Bind main board and display*
1. Drag and drop a “Connector Tool” to the drawing window
in LonMaker and connect “nvoToDisp” from main to
“nviFromMain” on the display.
2. Drag and drop a “Connector Tool” to the drawing window
in LonMaker and connect “nvoToMain” on the display to
“nviFromDisp” on the main.
3. To initiate communication between the main board and display,
cycle power twice to Vapor-logic
3
by disconnecting and then
reconnecting main power to the humidifier. Communication can
also be initiated by sending a Reset command to both the Main
and Keypad/display nodes in the Lon network manager.
Verify the Vapor-logic
3
configuration string
See Page 63 for instructions on how to use the System Set Up
menu to access and change the Vapor-logic
3
configuration string.
See Pages 32 and 33 for more information about the configuration
string.
When the humidifier demand is controlled by LonTalk, the last
position of the configuration string must be set to the letter L as
shown in the following list of options for that position:
//POFGPSPOPGG
$oPINIVNJEJTUBU
%o7%$IVNJEJTUBU
)o7%$IVNJEJTUBU
&oN"IVNJEJTUBU
L = Signal demand by others via LonTalk
9oN"USBOTNJUUFS
2%FXQPJOUUSBOTNJUUFS
44QFDJBM
Connecting LonTalk, continued
Service pin location
LED location
Figure 37-1:
Display service pin and LED locations
IMPORTANT
If you commission multiple humidifier
systems within BAS control scheme and
relocate any humidifier Vapor-logic
3
control components within the system,
you must decommission the component
controls at their present location and then
recommission them at their new location
and name.
IMPORTANT
* Tridium
®
users must make links as
described in “Bind main board and
display” steps 1 and 2 shown on this
page, and then go to the Link Manager
and execute a bind to create the LonTalk
bindings. Complete the binding process
by resetting the nodes or cycling power
as described in Step 3.