Installation and Operation Manual
8JSJOHTFOTPSEFWJDFTDPOUJOVFE
Variable air volume (VAV) option
This option is identified as a “V” in the third-from-last place
of your program code configuration string (for example:
EV11400285A7
VOX). See Pages 32-33 for more information about
the program code configuration string.
When the VAV control option is requested, DRI-STEEM provides a
duct mounted humidity transmitter (4 to 20 mA output, 0 to 100%
RH range). Install using shielded cable (see Figure 28-1).
The modulating high limit transmitter signal operates in
conjunction with the room or duct controlling transmitter
signal through the Vapor-logic
3
control system to prevent over
humidification in the duct. Vapor-logic
3
starts lowering the
humidifier output when the duct relative humidity is within 6% of
the duct high limit set point.
When this occurs, the message “VAV output limit” appears in the
keypad/display. If necessary, the reduction of the humidifier output
continues until maximum high limit set point is reached, shutting
off the humidifier completely.
When the high relative humidity starts to decrease in the duct,
Vapor-logic
3
slowly starts to increase the production of steam vapor.
When the duct relative humidity decreases to greater than 6% below
the duct high limit set point, the control transmitter is restored as
the primary controller, and the “VAV output limit” text no longer
appears in the keypad/display, returning the control system to
normal operation.
Figure 28-1:
VAV transmitter wiring
OM-2027d
Place shunt across
“I˝ pins of J15/18
when connecting
a 4-20 mA VAV
transmitter. See
Page 13 for more
information about
KVNQFSQJOT
J15/18
0 – 15 VDC
0 – 20 mA
0 – 150 ohm
RIV
OM-4030
VL3_IOM.pdf 32 11/19/2009 9:11:13 AM