Page 10 DRI-STEEM GTS Humidifier Installation, Operation, and Maintenance Manual
L o c a t i o n a n d c l e a r a n c e
r e c o m m e n d a t i o n s
Locating the humidifier
• Provide a level, solid foundation for the humidifier.
• Locate the humidifier as near as possible to a chimney or
outside wall so that the flue pipe from the humidifier is
short and direct.
• Locate the unit so it and its electrical components are
protected from water during humidifier operation and
service.
• Install the humidifier in a location away (and protected)
from drafts. If installed in a separate room, follow the
instructions concerning combustion and ventilation air.
• Locate the humidifier in an area where leakage from the
tank or its connections will not result in damage to the
adjacent structure or to lower floors of the structure.
When such locations cannot be avoided, install a suitable
drain pan (adequately drained) under the humidifier. The
pan must not restrict combustion airflow.
• Do not install the humidifier on carpeting, tile or other
combustible material other than wood flooring (indoor
application only).
• If located in an insulated space, keep the humidifier free
and clear of insulating materials. Insulating material can
be combustible. Inspect the humidifier area when the
humidifier is installed or when insulation is added.
Figure 10-1:
GTS clearance recommendations
18" (457 mm)
36" (914 mm)
30" (762 mm)
OM-1222
Note:
DRI-STEEM recommends a minimum of 1" (25 mm) clearance between hot surfaces and
combustible walls.
Installation