DRI-STEEM GTS Humidifier Installation, Operation, and Maintenance Manual • Page 37
Table 37-1:
Maximum steam carrying capacity and length of interconnecting vapor hose, tubing, and pipe*
Vapor hose
†††
Copper or stainless steel tubing
and Schedule 40 steel pipe
Hose I.D. Maximum capacity Maximum length** Tube or pipe size*** Maximum capacity
Maximum developed
length
†
inches DN lbs/hr kg/h ft m inches DN lbs/hr kg/h ft m
1½ 40 150 68 10 3 1½ 40 150 68 20 6
2 50 250 113 10 3 2 50 220 100 30 9
3
††
80
††
450 204 80 24
4
††
100
††
750 340 100 30
5
††
125
††
1400 635 100 30
6
††
150
††
2300 1043 100 30
* Based on total maximum pressure drop in hose, tubing, or pipe of 5" wc (1244 Pa)
** Maximum recommended length for vapor hose is 10' (3 m). Longer distances can cause kinking or low spots.
*** To minimize loss of capacity and efficiency, insulate tubing and pipe.
†
Developed length equals measured length plus 50% of measured length to account for pipe fittings.
††
Requires flange connection
†††
When using vapor hose, use DRI-STEEM vapor hose for best results. Field-supplied hose may have shorter life and may cause foaming in the evaporating
chamber resulting in condensate discharge at the dispersion assembly. Do not use vapor hose for outdoor applications.
D i s p e r s i o n : I n t e r c o n n e c t i n g p i p i n g
r e q u i r e m e n t s ( c o n t i n u e d )
Connecting humidifier to dispersion assembly with tubing or
pipe (continued)
• Insulating hard pipe reduces the loss in output caused by
condensation.
• When using hard pipe, take care to remove ALL traces of
lubricants used to thread the pipe. This minimizes the possibility
of tank foaming. Denatured alcohol or mineral spirits work best
for removing lubricant.
• If the humidifier must be located above the dispersion assembly,
use the recommend installation as shown on Page 38.
• See the maximum steam carrying capacity table below.
Installation