Vue de la page 61
Page 60 DRI-STEEM GTS Humidifier Installation, Operation, and Maintenance Manual
GTS standard water quality recommendations
The best way to determine how often your particular system needs
maintenance is to remove the probe plate and inspect it for mineral
deposits after three months of duty. Potable water carries a variety
of minerals and other materials in a mix that varies from location
to location. This variation in water quality, combined with the
hours of operation and duty cycle, will determine your own unique
maintenance schedule.
Water quality makes a difference
• Light to moderately hard water (2 to 10 grains hardness per
gallon [35 mg/L to 170 mg/L]) requires:
Annual cleaning
Regular skimming
• High mineral content water (more than 10 grains hardness per
gallon [more than 170 mg/L]) requires:
Cleaning frequency determined by use and water quality
Regular skimming
Periodic drain and flush cycles
• Softened water dramatically reduces mineral accumulation inside
standard water models.
(Note: Solids, like silica, are not removed in the softening
process.)
Adjusting skim duration
The skim time duration determines the quantity of water skimmed
with each fill cycle. Skim time is field adjustable using the
Vapor-logic4 keypad.
Each time the GTS refills, it fills to an elevation near the lip of the
skim/overflow fitting. A portion of the refill water then flows to the
drain carrying most of the minerals left by the previous evaporating
cycle. This reduces the mineral concentration, thereby reducing the
frequency of cleaning needed.
The heated water that flows to the drain is an operational cost.
Cleaning the humidifier also is an operational cost. Therefore,
DRI-STEEM recommends that the user observe and adjust the
skimming quantity to achieve a balance between minimizing
mineral buildup and conserving heated water.
M a i n t e n a n c e : G T S s t a n d a r d w a t e r
m o d e l s
Humidifier De-scaling solution
Scale buildup on humidifier heat exchangers
acts as an insulator, reducing humidifier
performance while increasing energy
costs. To keep humidifiers operating as
efficiently as possible, remove scale with
DRI-STEEM's Humidifier De-scaling Solution,
available for purchase from your DRI-STEEM
representative or distributor.
The De-scaling Solution cleans without risk
of corroding humidifier tanks or welds;
and there is no off-gassing, flammability,
or added heat risks associated with other
cleaning solutions. The De-scaling Solution
also cleans surfaces unreachable by hand
scraping.
DRI-STEEM's Humidifier De-scaling Solution
is the only approved cleaner/de-scaler for
use with DRI-STEEM humidifiers. Use of
other cleaners/de-scalers may void your
DRI-STEEM warranty.