DriSteem Vapor-Logic Spécifications Page 12

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 24
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 11
Page 12 • DRI-STEEM Vapormist humidifier
Drip-free dispersion basics
Guaranteed non-wetting distances
Using data collected in our on-site test lab, we have developed
guaranteed steam absorption (non-wetting) distances. Performance
charts allow you to confidently choose equipment that will
accommodate any application.
Dry steam
Adding humidification to an airstream without creating wetness
in the duct system is critical for the maintenance of a healthy
environment. Wet areas in ducts are a threat to the health of
building occupants since they moisten dust on duct floors, creating
ideal breeding grounds for disease-producing microbes. In addition,
water accumulating in ducts can drip and cause building damage.
Steam exits drip-free through tubelets
All DRI-STEEM evaporative dispersion tube units discharge steam
through thermal-resin tubelets fitted into dispersion tubes. These
tubelets extend from the center of the tube, where the steam is
driest, through the tube wall, to the duct airstream. In essence,
the tubelets provide a temperature-neutral exit tunnel for steam,
allowing steam to cross over lower-temperature metal without
condensing or dripping. Each tubelet contains a calibrated orifice
sized for steam capacity. These tubelets are a DRI-STEEM exclusive,
and are essential for drip-free steam dispersion.
Condensate drains away
Some condensation is inevitable in steam dispersion, but through
careful design, condensate can be controlled and directed away
from where it can cause problems.
For example, the Ultra-sorb dispersion panel has a unique double-
header design that uses gravity to remove condensate. Steam enters
the supply header, exits through the tubelets, and condensate drains
out the return header. In the Rapid-sorb dispersion unit, steam
enters one end of a single bottom header with velocities carefully
managed so that condensate is not pushed out into the air along
with the steam; it drains out at the opposite end of the header.
Reduce condensate, wasted energy with high-efficiency tubes
To significantly reduce condensate and wasted energy, use
DRI-STEEMs high-efficiency tubes, which reduce dispersion-
generated condensate and wasted energy by up to 85%. See
“High-efficiency Tube option” on Page 13.
mc_042610_1630
DRI-STEEM’s unique tubelets extend into the
center of the tube so only the driest steam is
discharged into the air.
Figure 12-2:
DRI-STEEM tubelets
Figure 12-1:
DRI-STEEM dispersion tubes
OM-150a
DRI-STEEM’s dispersion tubes are fitted with
one or two rows of closely-spaced thermal-
resin tubelets to evenly disperse steam across
the airstream.
Tubelet
Air flow
Condensate
Condensate
Steam
Steam
Steam
Steam
Steam
Steam
Calibrated
orifice
mc_042610_1550
mc_042610_1555