DriSteem Vapor-Logic Spécifications Page 5

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 24
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 4
DRI-STEEM Vapormist humidifier • Page 5
Vapormist principle of operation
1. When the system is first activated, the fill valve opens and the
evaporating chamber fills with water to the operating level.
2. On a call for humidity, the heating elements are energized,
causing the water to boil. The fill valve opens and closes as
needed to maintain the operating water level.
3. During refill in standard water systems, a portion of the surface
water is skimmed off, carrying away precipitated minerals.
DI/RO water systems (systems using deionized water or water
that has been treated using reverse osmosis) do not require
skimming.
4. Steam created in the evaporating chamber flows through vapor
hose or piping to the dispersion assembly, where it is discharged
into the airstream.
Figure 5-1:
Vapormist principle of operation
Standard water system (shown with cover removed)
OM-2000
2
3
4
1
Vue de la page 4