15
Keypad/display installation.
Installation
Installation:
Keypad/display installation
Installing modular cable
IMPORTANT: When routing modular cable
inside the control cabinet, route cable away from all
power wiring and connect the male modular plug into
the VAPOR-LOGIC
®
3
printed circuit board-mounted
female modular receptacle, J2. Push male plug in
until you hear a “click.” (The cable should be
plugged into the keypad/display as well.) The six-
wire cable provides the AC power to the keypad/
display and completes the FTT-10A-type digital
communication between the keypad/display and the
VAPOR-LOGIC
3
control board.
CAUTION: If a longer cable is needed, do not
attempted to fabricate one. Improper wiring can
permanently damage the VAPOR-LOGIC
3
board,
keypad or display. Please contact your local
DRI-STEEM representative for longer cable options.
Installing the keypad/display
IMPORTANT: Do not locate the keypad/display
inside the control cabinet. The hardware is
premounted in the keypad/display case with front
access to the digital display and keypad. Position the
case in a convenient location for easy access.
Note that the keypad/display requires an ambient
temperature range of 32°F to 122°F (0°C to 50°C) to
operate properly. Exceeding these limits will result in
a poor reading or no reading at all.
We recommend that you mount the keypad/display to
a surface using a field-supplied network phone wall
plate. To mount, simply slide the keypad/display onto
the tabs on the phone plate.