Aquastat operation
The aquastat set point is the minimum tank
temperature the VAPOR-LOGIC
®
3
controller should
maintain. It is adjusted through the Set Up screen.
This feature is typically used to keep the tank from
freezing in a cold environment. However, it can also
be used to hold a higher minimum temperature if a
quick response to a demand signal is needed. For
example, if the aquastat is set at 180°F (82°C), when
a call for humidity occurs, the tank will only need to
warm up 32°F (18°C) to reach the boiling point and
start producing steam. However, if the aquastat is at
its minimum setting of 40°F (4°C) and the tank is in
an average-temperature occupied room, the tank will
be sitting at about 70°F (21°C). Now, when a call for
humidity occurs, the tank will need to warm up
142°F (79°C) to reach the boiling point and begin
producing steam. This feature is standard on all
DRI-STEEM humidifiers with VAPOR-LOGIC
3
control except ULTRA-FOG
®
and Steam Injection
humidifiers.
Tank heat-up feature
The tank heat-up feature uses the tank temperature
sensor to quickly heat a tank in response to a demand
signal. Its operation is as follows: If the tank is cold
(70°F) and a small demand signal is delivered, the
VAPOR-LOGIC
3
controller will override the
demand signal and run the humidifier at 100%
demand until the tank temperature is 190°F (88°C). At
this point, control will be returned to the original
demand signal and the humidifier will begin normal
operation. This allows the system to respond quickly
to even the smallest demand. This feature is standard
on all DRI-STEEM humidifiers with
VAPOR-LOGIC
3
control except ULTRA-FOG and
Steam Injection humidifiers.
SDU timer
If your humidifier is equipped with a Space
Distribution Unit (SDU) or an Area-Type fan, you
have the option of controlling how long the fan will
run after a call for humidity has ended. This delay
(SDU Duration) is adjustable in one-minute intervals
through the Set Up screen.
Sensor offsets
All external transmitters shipped with
VAPOR-LOGIC
3
can be field calibrated using the
keypad/display through the Set Up screen. For
example, if the system is equipped with an RH
transmitter, there will be an RH offset setting. The
factory default for all transmitter settings is zero.
However, if an adjustment is necessary, the keypad
can be used to adjust the transmitter reading up or
down through this setting. The sensors that have this
adjustment capability are the humidity, VAV high
limit, temp comp and dew point transmitters.
Metric conversion
VAPOR-LOGIC
3
is capable of displaying all
information in metric as well as standard units.
Aquastat, heat-up, SDU, offsets, metric.
Operation
Operation:
Aquastat, heat-up, SDU, offsets, metric