No control voltage
present
Heater fuses open
Transformer
secondary circuit
breaker tripped
Field wiring not
installed
Field-supplied remote
fault indicator lamp is
burned out.
Remote fault
VAPOR-LOGIC
3
relay is not switching.
No power, or
incorrect voltage to
VAPOR-LOGIC
3
board
Modular
communication cable
is disconnected.
Open, shorted, or
incorrect wiring of
transmitter
Open, shorted, or
incorrect wiring of
transmitter.
Operation
Operation:
Troubleshooting guide
Troubleshooting guide.
1
2
3
4
5
Green power indicator
light is off.
No remote fault
indication
No readable
information on
keypad/display
Humidity transmitter
fault
Dew point transmitter
fault
Check for proper supply voltage.
Check heater fuses for voltage present
at transformer.
Check for wiring shorts; reset breaker.
Provide field wiring to a remote fault
indicator from VAPOR-LOGIC
®
3
terminal block J22.
Check if lamp by others is burned out;
replace if needed.
Check relay continuity
(VAPOR-LOGIC
3
terminal J22) for
contact closure.
Check main power supply.
Connect modular cable.
Check wiring terminals
(VAPOR-LOGIC
3
terminal J26) for
correct wiring and voltages.
Check wiring terminals
(VAPOR-LOGIC
3
terminal J26) for
correct wiring and voltages.
Problem
number
Problem Possible cause Action
More on next page ...